| MATERIAL |
|
SOLID lbs.
(cu. ft.) |
LIQUID Gallons
(lbs.) |
| *Corrosives |
Base |
1,000 |
100 |
| Sprinklered (no Cabinet) |
2,000 |
200 |
| Cabinet (unsprinklered) |
1,000 |
100 |
| Cabinet, Sprinklered |
2,000 |
200 |
| Highly Toxics |
Base |
3 |
(3) |
| Sprinklered (no Cabinet) |
6 |
(6) |
| Cabinet (unsprinklered) |
3 |
(3) |
| Cabinet, Sprinklered |
6 |
(6) |
| Irritants |
Base |
**5,000 |
**500 |
| Sprinklered (no Cabinet) |
**10,000 |
**1,000 |
| Cabinet (unsprinklered) |
**5,000 |
**500 |
| Cabinet, Sprinklered |
**10,000 |
**1,000 |
| Sensitizers |
Base |
**5,000 |
**500 |
| Sprinklered (no Cabinet) |
**10,000 |
**1,000 |
| Cabinet (unsprinklered) |
**5,000 |
**500 |
| Cabinet, Sprinklered |
**10,000 |
**1,000 |
| Other Health Hazards |
Base |
**5,000 |
**500 |
| Sprinklered (no Cabinet) |
**10,000 |
**1,000 |
| Cabinet (unsprinklered) |
**5,000 |
**500 |
| Cabinet, Sprinklered |
**10,000 |
**1,000 |
| Toxics |
Base |
125 |
(125) |
| Sprinklered (no Cabinet) |
250 |
(250) |
| Cabinet (unsprinklered) |
125 |
(125) |
| Cabinet, Sprinklered |
250 |
(250) |
Back